1.

  Do clean agents “suck” the oxygen out of the room like the old Halon systems?

No! It is a misconception that Halon “sucks” the oxygen out of a room or hazard area. Clean agents, such as FM-200, Inergen, Novec 1230 and even Halon, do not extinguish fires by the removal of oxygen. Most clean agent suppression agents work on the primary principle of heat absorption with some chain breaking mechanism to extinguish fire. These products are designed and installed as “people friendly” or “life safe” extinguishing agents. They are used in occupied spaces for just such a reason. These agents have undergone rigorous testing for applications where people may be present.
 
       
2.   Can I take the sprinklers out of my room if I install a clean agent system?

We recommend that the existing water sprinkler be maintained in the room. The clean agent system will operate far in advance of the sprinkler system. Therefore, the water sprinkler system serves as an excellent compliment to the clean agent systems. Please consider that the sprinkler system will protect the building and not the contents.

In many local areas, the fire marshal/inspector’s office will not allow you to totally remove water sprinkler protection. However, alternatives to standard “wet sprinklers” such as “pre-action dry pipe systems” are available.

In all cases a qualified fire protection contractor should be consulted to determine the most advantageous solution. Healey Fire Protection would be happy to discuss the design requirements of your local fire official.
 
       
3.   Do I have to install safety upgrades on all my CO-2 (Carbon Dioxide) systems?

Yes, by December 31, 2008, mandatory personnel safety upgrades are required on all total flooding CO-2 systems where people are present. The recent changes to NFPA Standard 12 (National Fire Protection Association – Standard on Carbon Dioxide Extinguishing Systems) outline the type of system and protected areas that require upgrades. These systems include total flooding and local application CO-2 systems that protect an “occupied” or “occupiable” space/area. Consideration should also be given to the areas near or around the protected space where the CO-2 gas could migrate.

The primary goal of the mandatory retrofits (safety upgrades) is to provide enhanced protection against exposure of personnel to potentially dangerous concentrations of CO-2 from the discharge of a fire protection system. Healey Fire Protection will conduct an onsite survey to evaluate the need of the CO-2 system safety upgrades.
 
       
4.   Can CO-2 (Carbon Dioxide) systems still be installed?

Yes, carbon dioxide systems can still be installed and used, but you should consider the other alternatives first. Consideration must be given to the hazard or area being protected to determine if CO-2 is a suitable agent. CO-2 should not be used in an “occupied” or “occupiable” space/area unless no other alternatives are available or practical. Definitions on where and when a CO-2 system can be used are outlined in NFPA-12 (National Fire Protection – Standard on Carbon Dioxide Extinguishing Systems). Healey Fire Protection can analyze your potential hazardous area to recommend the proper system.
 
       
5.  

Aren’t all water mist systems the same?

No, there are many types of water mist systems. Water mist or water spray systems are divided into three categories: Low, Intermediate and High Pressure Systems. As water mist/spray systems increase in pressure (psi) they reduce the amount of water that is required to extinguish a fire. For example, a high pressure system can extinguish a fire with much less water than a standard wet sprinkler system. Healey Fire Protection can analyze your potential hazardous area to recommend the proper system.

 
       
6.   What are the requirements for installing and maintaining a Special Hazards Fire System?

The National Fire Protection Association (NFPA) has set guidelines for the installation and testing of fire protection systems. Special hazard systems present very unique and site specific concerns. Most fire suppression systems should be fully tested every 6 months as a requirement of your insurance company, state and local fire authorities.

A qualified fire professional should always be consulted when working with a Fire Suppression System. Membership and participation in the following associations are a MUST when identifying a qualified company:

NFPA Membership www.nfpa.org
FSSA Membership www.fssa.net
NICET Certified Engineers and Technicians www.nicet.org
SFPE Membership www.sfpe.org

Healey Fire Protection is a qualified fire protection contractor for the installation and maintenance of your special hazard fire protection systems.
 
       
7.   Will the addition of a special hazard fire system reduce my insurance premiums?

Yes, in many cases the installation of a special hazard fire protection system can reduce your insurance premiums. If you are interested in adding a special hazard fire protection system, contact your insurance carrier and let them know of the added benefits and reduction in property loss and down time. A reduction in your insurance premium may offset the initial expense of a special hazard system. Feel free to contact a Healey Fire Protection representative to ensure that you have all the information that your insurer may request.
 
       
8.   Are there advantages/disadvantages in regards to which clean agent I choose?

Yes, each agent has its own characteristics and advantages. Although many of the agents work under similar principles of suppression, they each have their own advantages. There are also distinct applications or types of hazards that differentiate which agent to choose. For over 45 years, Healey Fire Protection has provided special hazard fire suppression systems to protect a myriad of applications. Chances are we already have a design that will meet your fire protection needs.
 
       
9.   Do I need a room exhaust system to evacuate the fire products of combustion and clean agent?

Exhaust systems are not required per NFPA 2001. They are noted in the appendix, but not required. In very few cases, an exhaust or purge fan system is required. Some local AHJ’s (authority having jurisdiction) or local fire marshal/inspector’s offices require these types of evacuation systems.

The clean agent system employs early warning smoke detection that prevents higher levels of decomposition products by sensing and suppressing the fires at a very early stage. Therefore, when personnel enter the room, their exposure to possible decomposition byproducts is kept to a minimum.

Healey Fire Protection will review the requirements of NFPA 2001 with your local authority.
 
       
10.   Do I need to have a computer power and air conditioning shutdown upon discharge of my clean agent system?

Yes, NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems and NFPA 75, Standard for the Protection of Information Technology Equipment both call for the shut down of air handling systems. The continued operation of the air handling systems would negatively impact the concentration of the clean agent. NFPA 75 requires the power to all electronic equipment shall be disconnected upon activation of a gaseous agent system. Without de- energizing the equipment, an electrical fire may reignite.
 
       
11.
  Will my new clean agent system be eventually "banned" like Halon was?

Halon is not “banned”. New Halon systems can no longer be installed and most of the existing systems cannot be modified. Halon is no longer being produced; however, in some cases, your existing Halon system can be recharged using reclaimed (used) gas. There is no information regarding the banning of alternative or “new clean agent” systems. The agents that are sold today are the cleanest and most environmentally friendly fire suppression systems ever produced. There is no way to predict the future requirements that will be adopted by groups like the U.S. EPA (Environmental Protection Agency) or NFPA (National Fire Protection Association), but in our opinion, the new clean agent gases will be available for decades to come.
 
       
12.   My Halon 1301 system discharged, can it be recharged or does it have to be replaced with a new clean agent system?

There is no mandate in the U.S. to replace Halon systems. It is a good practice to consider replacing or upgrading any existing Halon system even if you haven’t had a discharge. Halon is no longer being produced. However, in some cases, your existing Halon system can be recharged using reclaimed (used) gas. As the existing Halon supply is being used the cost of reclaimed gas is expected to increase exponentially with the demand.

Healey Fire Protection can review your existing Halon System to develop a budgetary proposal for replacement with an appropriate clean agent system.
 
       
13.  

Can I modify my existing Halon 1301 system?

No. New Halon systems have not been installed since 1993. Manufacturers have since discontinued manufacturing or listing Halon equipment. Some of the existing piping may be utilized in the installation of a new clean agent system, assuming it meets the required type and grade. A field survey of the piping network would determine how much of the piping could be reused.


Back to top

 

 

 


 
 
© 2006 Healey Fire Protection, Inc.